Report: 1943 SF - Sample Address: 433 Main Blvd

Confidential Inspection Report 433 Main Blvd Central, CA 99995

Prepared for: John Doe

This report is the exclusive property of the inspection company and the client whose name appears herewith and its use by any unauthorized persons is prohibited.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 2 Report: 1943 SF - Sample Address: 433 Main Blvd

Report Table of Contents GENERAL INFORMATION

7

GROUNDS

9

EXTERIOR - FOUNDATION

17

BASEMENT - CRAWLSPACE

19

ROOF SYSTEM

21

ELECTRICAL SYSTEM

25

HEATING - AIR CONDITIONING

31

PLUMBING SYSTEM

35

KITCHEN - APPLIANCES

41

BATHROOMS

44

INTERIOR ROOMS

52

LAUNDRY AREA

59

GARAGE - CARPORT

61

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 3 Report: 1943 SF - Sample Address: 433 Main Blvd

July 21, 2017 John Doe 643 Hornsby Road Canyon Country, CA 91351 RE:

433 Main Blvd Central, CA 99995

Dear John: At your request, a visual inspection of the above referenced property was conducted on . An earnest effort was made on your behalf to discover all visible defects, however, in the event of an oversight, maximum liability must be limited to the fee paid. The following is an opinion report, reflecting the visual conditions of the property at the time of the inspection only. Hidden or concealed defects cannot be included in this report. No warranty is either expressed or implied. This report is not an insurance policy, nor a warranty service. IMPORTANT: The Summary is not the entire report. The complete report may include additional information of concern to the client. It is recommended that the client read the complete report. The entire Inspection Report, including the Standards of Practice, limitations and scope of Inspection, and Pre-Inspection Agreement must be carefully read to fully assess the findings of the inspection. This list is not intended to determine which items may need to be addressed per the contractual requirements of the sale of the property. Any areas of uncertainty regarding the contract should be clarified by consulting an attorney or real estate agent. It is strongly recommended that you have appropriate licensed contractors evaluate each concern further and the entire system for additional concerns that may be outside our area of expertise or the scope of our inspection BEFORE the close of escrow. Please call our office for any clarifications or further questions.

OBSERVATIONS GROUNDS Front Porch: Slab: Raised, flagstone. Handrails recommended. Decks / Balcony: Condition: Grout/Caulking/Sealant recommended at all joint areas, to avoid hidden moisture intrusion/damage (MM)

Fences & Gates: Condition: Unable to fully inspect due to cover. Grading: Site: Underground drain system present, not tested. Maintain and flood test regularly System appears to need some maintenance.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 4 Report: 1943 SF - Sample Address: 433 Main Blvd

Landscaping: Condition: Trim plants away from structure. Foliage growth on the structure promotes pest invasion, and moisture damage to wall cladding and trim (MM)

Trees are touching or overhanging the roof. Damage is possible. Trees touching the roof promote rodent activity in the attic areas.

EXTERIOR - FOUNDATION Exterior Walls: Materials & Condition: Cracks noted are typical (shrinkage type), Monitor cracks for growth, and maintain by sealing cracks larger than 1/8" with an expandable sealant. Flashing & Trim: Water damage noted in some areas, recommend further evaluation by licensed Structural Pest Control report.(MM) BASEMENT - CRAWLSPACE Crawlspace: Access: South access viewed. Unable to access at time of inspection due to semi-permanent flagstone placement (buried) in front of cover. Recommend making this side fully accessible for maintenance. Ventilation: Some vents were dirty/blocked, maintenance recommended for proper cros flow to crawlspace (MM) ROOF SYSTEM Eaves - Soffits - Fascias: Water stains/damage noted in some areas, recommend further evaluation by licensed Structural Pest Control report.(MM) Some peeling paint viewed at S/E corner. Maintenance recommended by a qualified professional. Gutters & Downspouts: Consider installing rain gutters and downspouts to help with site drainage and potential water damage to wall areas.

ELECTRICAL SYSTEM Electrical Distribution Panels: Main Panel Observations: Missing handle tie/coupler at the 50/240 breaker for sub panel (MM) Correction recommended. Electrical Outlets: General: No power, unable to reset GFCI (prior to finding the master outlet at the kitchen) This GFCI outlet was found to be redundant to kitchen GFCI ,LH side of sink.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 5 Report: 1943 SF - Sample Address: 433 Main Blvd

Recommend a full cover on exterior outlets with a dedicated plug. Ground Fault Circuit Interrupter (GFCI) outlets are recommended for installation at exterior areas. Outlet viewed at driveway area. GFCI - inoperable at north side exterior wall. Recommend further evaluation and correction by licensed electrician. HEATING - AIR CONDITIONING Heating Equipment: Air Filters: The filter is in need of cleaning or replacement. Replacing or cleaning filters every 90 days is recommended. Viewed at hallway ceiling / 2nd floor. Fireplaces / Solid Fuel Heating: Living Room: There is a visible build-up of creosote in the firebox or flue which indicates a need for cleaning. A professional chimney sweep should be consulted. Creosote is a tar-like substance that is created by burning wood fuels. It often lines the upper part of the firebox and flue. If not removed, this build-up can create a fire hazard. The age and condition of this fireplace is such that it should be fully inspected and evaluated by a licensed professional chimney sweep prior to use. Air Conditioning: System Condition: A whistling noise was present at the master bathroom register while AC was operating. The same noise was NOT present while operating the heater. Unable to determine the cause of this sound. You may choose to have further evaluation by a licensed HVAC specialist. Condensate Line: Condensate lines installed. PLUMBING SYSTEM Water Heater: Condition: Vent flue is loose, or disconnected. Missing fasteners at the upper and lower joints. Recommend repairs by a qualified professional. BATHROOMS Sink & Cabinetry: Hall Bath: Fittings are worn and corrosion is noted. Monitor and maintain. Guest Bath / 1st Floor: Leaks at faucet handles. A licensed plumber should be called to make further evaluation and repairs as needed. Tub/Shower Fixtures: Master Bath: Minor leakage is noted at faucet handles (tub) Monitor and maintain. Tub/Shower And Walls: Master Bath: Whirlpool tub noted, not tested. API does not test whirlpool tubs. It is recommended that the lines be cleaned regularly to avoid bacterial contamination.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 6 Report: 1943 SF - Sample Address: 433 Main Blvd

Unit responded to power switch Unable to verify the presence/location of a GFCI protected power source. Recommend further evaluation by a qualified electrician to verify for safety. Cover panel not removed. Caulk and seal all tub, shower, and floor areas as a precaution. Grout needs some maintenance at the tub area. Cosmetic moisture damage is noted at the wall or floor outside the tub/shower area. Area viewed near leaking tub handles. Mildew noted in area, recommend cleaning and disinfecting on a regular basis (MM) Hall Bath: Cosmetic moisture damage is noted at the wall or floor outside the tub/shower area. Caulk and seal all tub, shower, and floor areas as a precaution. INTERIOR ROOMS Doors: Other Exterior Doors: French doors viewed at 2nd floor balcony: Moisture damage noted a base areas. Make repairs and maintenance as needed. Door hardware needs some adjustment or repair for it to function appropriately (loose knob, etc.) GARAGE - CARPORT Garage Walls: Type & Condition: Drywall, General condition appears serviceable Unable to fully inspect, due to occupant belongings, and/or wall covering.

ITEMS NEEDING ACTION ELECTRICAL SYSTEM Electrical Outlets: General: Non grounded outlet noted at exterior wall (patio door area), upgrades needed for safety. GFCI - inoperable, probably due to improper ground wire. Recommend further evaluation and correction by licensed electrician.

Thank you for selecting our firm to do your pre-purchase home inspection. If you have any questions regarding the inspection report or the home, please feel free to call us.

Sincerely, Jerry Pontius, CMI Accredited Property Inspection 951-318-5544

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 7 Report: 1943 SF - Sample Address: 433 Main Blvd

GENERAL INFORMATION Client & Site Information: Rear view.

Inspection Date:

July 3, 2017 10:00 AM.

Client:

John Doe 643 Hornsby Road Canyon Country, CA 91351

Inspection Site:

433 Main Blvd Central, CA 99995.

House Occupied?

Yes.

People Present:

Homeowner.

Comments:

This residence was occupied at time of inspection. Viewing is limited due to occupant belongings. It is not possible to test all electrical outlets, and view all wall, and ceiling areas. Recommend carefully viewing these areas at time of final walk through.

Building Characteristics: Main Entry Faces:

West.

Estimated Age:

1949, remodeled in 1987 (public record) and more recently in 2002? square footage = 2116

Approximate

Check all applicable permits and seller disclosures. Building Type:

1 family.

Stories:

2

Space Below Grade:

Crawl space.

Climatic Conditions: Weather:

Overcast.

Soil Conditions:

Damp, In landscaped areas.

Outside Temperature (f):

60-70.

Utility Services: Water Source:

Public.

Sewage Disposal:

Public.

Utilities Status:

All utilities on.

About Rated Items: Items not found in this report are beyond the scope of this inspection and should not be considered inspected at this time. Please read the entire report for important details. Inspected items may be generally rated as follows: OK = "Serviceable" = Item is functional and we did not observe conditions that would lead us to believe problems existed with this system or component. Some serviceable items may show wear and tear. Other conditions may be noted in the body of the report. MM = "Marginal/Maintenance" = Item warrants attention or monitoring, or has a limited remaining useful life expectancy and may require replacement in the not too distant future. Further evaluation or servicing may be needed by a qualified licensed contractor

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 8 Report: 1943 SF - Sample Address: 433 Main Blvd

or specialty tradesman dealing with that item or system. RR = "Repair or Replace" = Item, component, or unit is not functioning as intended and needs repair or replacement. Further evaluation is needed by a qualified licensed contractor or specialty tradesman dealing with that item or system.

REPORT LIMITATIONS This report is intended only as a general guide to help the client make his own evaluation of the overall condition of the home, and is not intended to reflect the value of the premises, nor make any representation as to the advisability of purchase. The report expresses the personal opinions of the inspector, based upon his visual impressions of the conditions that existed at the time of the inspection only. The inspection and report are not intended to be technically exhaustive, or to imply that every component was inspected, or that every possible defect was discovered. No disassembly of equipment, opening of walls, moving of furniture, appliances or stored items, or excavation was performed. All components and conditions which by the nature of their location are concealed, camouflaged or difficult to inspect are excluded from the report. The inspection is performed in compliance with generally accepted standard of practice, a copy of which is available upon request. Systems and conditions which are not within the scope of the inspection include, but are not limited to: formaldehyde, lead paint, asbestos, toxic or flammable materials, and other environmental hazards; pest infestation, playground equipment, efficiency measurement of insulation or heating and cooling equipment, internal or underground drainage or plumbing, any systems which are shut down or otherwise secured; water wells (water quality and quantity) zoning ordinances; intercoms; security systems; heat sensors; cosmetics or building code conformity. Any general comments about these systems and conditions are informational only and do not represent an inspection. The inspection report should not be construed as a compliance inspection of any governmental or non governmental codes or regulations. The report is not intended to be a warranty or guarantee of the present or future adequacy or performance of the structure, its systems, or their component parts. This report does not constitute any express or implied warranty of merchantability or fitness for use regarding the condition of the property and it should not be relied upon as such. Any opinions expressed regarding adequacy, capacity, or expected life of components are general estimates based on information about similar components and occasional wide variations are to be expected between such estimates and actual experience. We certify that our inspectors have no interest, present or contemplated, in this property or its improvement and no involvement with tradespeople or benefits derived from any sales or improvements. To the best of our knowledge and belief, all statements and information in this report are true and correct. Should any disagreement or dispute arise as a result of this inspection or report, it shall be decided by arbitration and shall be submitted for binding, non-appealable arbitration to the American Arbitration Association in accordance with its Construction Industry Arbitration Rules then obtaining, unless the parties mutually agree otherwise. In the event of a claim, the Client will allow the Inspection Company to inspect the claim prior to any repairs or waive the right to make the claim. Client agrees not to disturb or repair or have repaired anything which may constitute evidence relating to the complaint, except in the case of an emergency.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 9 Report: 1943 SF - Sample Address: 433 Main Blvd

GROUNDS This inspection is not intended to address or include any geological conditions or site stability information. We do not comment on coatings or cosmetic deficiencies and the wear and tear associated with the passage of time, which would be apparent to the average person. However, cracks in hard surfaces can imply the presence of expansive soils that can result in continuous movement, but this can only be confirmed by a geological evaluation of the soil. Any reference to grade is limited to only areas around the exterior of the exposed areas of foundation or exterior walls. We cannot determine drainage performance of the site or the condition of any underground piping, including subterranean drainage systems and municipal water and sewer service piping or septic systems. Decks and porches are often built close to the ground, where no viewing or access is possible. Any areas too low to enter or not accessible are excluded from the inspection. We do not evaluate any detached structures such as storage sheds and stables, nor mechanical or remotely controlled components such as driveway gates. We do not evaluate or move landscape components such as trees, shrubs, fountains, ponds, statuary, pottery, fire pits, patio fans, heat lamps, and decorative or low-voltage lighting. Any such mention of these items is informational only and not to be construed as inspected.

Paving Conditions: Driveway:

OK þ

MM RR ¨ ¨ Flagstone.

Walks:

þ

¨

¨

Sidewalk type: Flagstone.

þ

¨

¨

Sidewalk type: Flagstone (loose) Viewed at south side.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 10 Report: 1943 SF - Sample Address: 433 Main Blvd

OK þ

MM RR ¨ ¨ Sidewalk type: Concrete Viewed ta north side.

¨

¨

¨

Underground drain system present, not tested. Maintain and flood test regularly.

Patio / Porch:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 11 Report: 1943 SF - Sample Address: 433 Main Blvd

þ

¨

Slab:

OK þ

MM RR þ ¨ Raised, flagstone. Handrails recommended.

Structure:

þ

¨

¨

Type: Same as structure.

Cover / Roof:

þ

¨

¨

Same as main roof. See Roofing page.

þ

¨

¨

Front Balcony viewed: structure.

þ

¨

¨

Tile deck surface. Unable to view/verify moisture barrier below tile surface. Maintain deck surface.

Slab:

¨

Type: Flagstone.

Front Porch:

Decks / Balcony: Condition:

© Accredited Property Inspection

Same as

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 12 Report: 1943 SF - Sample Address: 433 Main Blvd

¨

þ

¨

OK þ

MM RR ¨ ¨ Type: Stucco facade. Unable to view/identify base materials.

þ

¨

Grout/Caulking/Sealant recommended at all joint areas, to avoid hidden moisture intrusion/damage (MM)

Fences & Gates: Condition:

© Accredited Property Inspection

¨

Same as above.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 13 Report: 1943 SF - Sample Address: 433 Main Blvd

¨

þ

¨

OK þ

MM RR ¨ ¨ Flat site, Grade at foundation appears serviceable, Underground drain system present, not tested. Maintain and flood test regularly þ ¨ Underground drain system present, not tested. Maintain and flood test regularly System appears to need some maintenance.

Unable to fully inspect due to cover.

Grading: Site:

¨

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 14 Report: 1943 SF - Sample Address: 433 Main Blvd

¨

¨

¨

OK ¨

MM RR þ ¨ Trim plants away from structure. Foliage growth on the structure promotes pest invasion, and moisture damage to wall cladding and trim (MM)

Possible clogged underground drain viewed in front planter. Recommend further evaluation and maintenance by a qualified professional.

Landscaping: Condition:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 15 Report: 1943 SF - Sample Address: 433 Main Blvd

© Accredited Property Inspection

¨

¨

¨

OK ¨

MM RR þ ¨ Trees are touching or overhanging the roof. Damage is possible. Trees touching the roof promote rodent activity in the attic areas.

¨

¨

¨

Same as above.

Planter boxes noted at structure, these cause water to hold against the side of the building. Monitor for possible moisture penetration, and add drainage. exterior wall (north), NOT tested.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 16 Report: 1943 SF - Sample Address: 433 Main Blvd

OK ¨

© Accredited Property Inspection

MM RR ¨ ¨ Irrigation systems are not part of this inspection (MM)

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 17 Report: 1943 SF - Sample Address: 433 Main Blvd

EXTERIOR - FOUNDATION All structures are dependent on the soil beneath them for support, but soils are not uniform. Some that appear to be firm and solid can become unstable during seismic activity or may expand with the influx of water, moving structures with relative easy and fracturing slabs and other hard surfaces. In accordance with our standards of practice, we identify foundation types and look for any evidence of structural deficiencies. However, minor cracks or deteriorated surfaces are common in many foundations and most do not represent a structural problem. If major cracks are present along with bowing, we routinely recommend further evaluation be made by a qualified structural engineer. All exterior grades should allow for surface and roof water to flow away from the foundation. All concrete floor slabs experience some degree of cracking due to shrinkage in the curing process. In most instances floor coverings prevent recognition of cracks or settlement in all but the most severe cases. Where carpeting and other floor coverings are installed, the materials and condition of the flooring underneath cannot be determined. Areas hidden from view by finished walls or stored items cannot be judged and are not a part of this inspection. We will certainly alert you to any suspicious cracks if they are clearly visible. However, we are not specialists, and in the absence of any major defects, we may not recommend that you consult with a foundation contractor, a structural engineer, or a geologist, but this should not deter you from seeking the opinion of any such expert. We also routinely recommend that inquiry be made with the seller about knowledge of any prior foundation or structural repairs.

Exterior Walls: Materials & Condition:

Flashing & Trim:

© Accredited Property Inspection

OK þ

MM RR ¨ ¨ Walls are constructed with: Stucco (smooth)

¨

þ

¨

Cracks noted are typical (shrinkage type), Monitor cracks for growth, and maintain by sealing cracks larger than 1/8" with an expandable sealant.

¨

¨

¨

Same as above.

þ

¨

¨

Metal materials, Wood materials. Recently painted.

¨

þ

¨

Water damage noted in some areas, recommend further evaluation by licensed Structural Pest Control report.(MM)

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 18 Report: 1943 SF - Sample Address: 433 Main Blvd

Chimney: Please Note:

There are a wide variety of chimneys and interrelated components. However, there are three basic types, single-walled metal, masonry, and pre-fabricated metal ones that are commonly referred to as factory-built ones. Single-walled metal ones should not be confused with factory-built metal ones, and are rarely found in residential use, but masonry and factory-built ones are commonplace. Our inspection of them conforms to industry standards, and is that of a generalist and not a specialist. However, significant areas of chimney flues cannot be adequately viewed during a field inspection. Therefore, because our inspection of chimneys is limited to areas easily viewed and does not include the use of specialized equipment, we will not guarantee their integrity or drafting ability and recommend that they be more thoroughly evaluated before the close of escrow.

Chimney Exterior:

OK þ

MM RR ¨ ¨ Stucco materials. South side.

Flue:

¨

¨

¨

The inspection is limited to the visible portions of the fireplace flue. Drop light, mirrors, and smoke testing are not a part of the inspection. Visibility is limited to less than 20% of the flue. If further investigation is recommended, the services of a qualified professional chimney sweep should be obtained.

Flashing:

¨

¨

¨

Not fully visible, Satisfactory - The installed flashing around the chimney stack appears to be functional.

Chimney Cap:

þ

¨

¨

The chimney cap is made of metal. Its function is to keep water out of the stack. It appears to be functioning as intended.

Materials & Condition:

þ

¨

¨

Poured Concrete stem walls. Satisfactory - The exposed portions of the perimeter foundation walls appear to be adequate.

Recent Movement:

There is no evidence of any recent movement.

Foundation:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 19 Report: 1943 SF - Sample Address: 433 Main Blvd

BASEMENT - CRAWLSPACE While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. During the course of the inspection, the inspector does not enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely affect the health of the inspector or other persons.

Crawlspace: Access:

Crawl space viewing is limited-to viewing at north side. This access is to a small area under the kitchen only. This inspection does not cover the presence or lack of wood destroying insects.

OK ¨

MM RR þ ¨ South access viewed. Unable to access at time of inspection due to semi-permanent flagstone placement (buried) in front of cover. Recommend making this side fully accessible for maintenance.

Walls:

þ

¨

¨

Walls are poured concrete. Exposed portions of the interior foundation perimeter walls appear to be satisfactory.

Foundation Bolts:

þ

¨

¨

This inspection noted the presence of foundation bolts correctly used to secure the framing to the foundation.

Beams/Underfloor:

þ

¨

¨

Satisfactory - The main structure installed appears to be in satisfactory condition.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 20 Report: 1943 SF - Sample Address: 433 Main Blvd

Ventilation:

Floor:

© Accredited Property Inspection

OK þ

MM RR ¨ ¨ Satisfactory - The cross-ventilation in the crawlspace appears to be adequate.

¨

þ

¨

Some vents were dirty/blocked, maintenance recommended for proper cros flow to crawlspace (MM)

þ

¨

¨

Soil.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 21 Report: 1943 SF - Sample Address: 433 Main Blvd

ROOF SYSTEM Although not required to, we generally attempt to evaluate various roof types by walking on their surfaces. If we are unable or unwilling to do this for any reason, we will indicate the method used to evaluate them. Every roof will wear differently relative to its age, number of layers, quality of material, method of application, exposure to weather conditions, and the regularity of its maintenance. We can only offer an opinion of the general quality and condition of the roofing material. The inspector cannot and does not offer an opinion or warranty as to whether the roof leaks or may be subject to future leakage. The waterproof membrane beneath roofing materials is generally concealed and cannot be examined without removing the roof material. Although roof condition can be evaluated, it is virtually impossible for anyone to detect a leak except as it is occurring or by specific water tests, which are beyond the scope of our service. Even water stains on ceilings or on framing within attics will not necessarily confirm an active leak without some corroborative evidence, and such evidence can be deliberately concealed. We evaluate every roof conscientiously, and even attempt to approximate its age, but we will not predict its remaining life expectancy, or guarantee that it will not leak. Naturally, the sellers or the occupants of a residence will generally have the most intimate knowledge of the roof and of its history. Therefore, we recommend that you ask the sellers about it, and that you either include comprehensive roof coverage in your home insurance policy, or that you obtain a roof certification from an established local roofing company. We do not inspect attached accessories including by not limited to solar systems, antennae, and lightning arrestors.

Roof: Style:

Gable.

Roof Access:

Viewed from ground, inspection is limited. height/pitch/weather/type.

Roof Covering:

OK þ

MM RR ¨ ¨ Tile, Appears useful life

Unable to fully access due to

serviceable/within

TYPICAL MAINTENANCE RECOMMENDED. This usually consists of repair/replacement of damaged/missing/loose tiles. This maintenance should help insure the weather tightness of the building and should be performed on a regular basis. þ

© Accredited Property Inspection

¨

¨

Appears serviceable/within useful life.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 22 Report: 1943 SF - Sample Address: 433 Main Blvd

þ

¨

¨

OK þ

MM RR ¨ ¨ Metal.

þ

¨

¨

Appears serviceable The design of this structure offers little, or no overhang at the eave areas, this makes the exterior wall covering vulnerable to weather. Maintain sealant at all joint areas to avoid hidden water damage and possible moisture intrusion.

¨

þ

¨

Water stains/damage noted in some areas, recommend further evaluation by licensed Structural Pest Control report.(MM) Some peeling paint viewed at S/E corner. Maintenance recommended by a qualified professional.

¨

þ

¨

Consider installing rain gutters and downspouts to help with site drainage and potential water damage to wall areas.

Appears serviceable/within useful life.

Flashings:

Eaves - Soffits - Fascias:

Gutters & Downspouts:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 23 Report: 1943 SF - Sample Address: 433 Main Blvd

¨

¨

¨

Subsurface drains noted, but Not Tested. THEY ARE NOT PART OF THIS INSPECTION.

In accordance with our standards, we do not attempt to enter attics that have less than thirty-six inches of headroom, are restricted by ducts, or in which the insulation obscures the joists and thereby makes mobility hazardous, in which case we would inspect them as best we can from the access point. In regard to evaluating the type and amount of insulation on the attic floor, we use only generic terms and approximate measurements, and do not sample or test the material for specific identification. Also, we do not disturb or move any portion of it, and it may well obscure water pipes, electrical conduits, junction boxes, exhaust fans, and other components.

Attic & Insulation: Access:

Attic is full size, Viewing was limited to accessible areas.

Structure:

OK þ

MM RR ¨ ¨ A rafter system is installed in the attic cavity to support the roof decking. The rafters or truss system appears to be in satisfactory condition.

þ

¨

¨

The rafters or truss system appears to be in satisfactory condition.

þ

¨

¨

The roof decking plywood sheeting.

© Accredited Property Inspection

material

is

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 24 Report: 1943 SF - Sample Address: 433 Main Blvd

OK þ

MM RR ¨ ¨ The rafters or truss system appears to be in satisfactory condition.

þ

¨

¨

The rafters or truss system appears to be in satisfactory condition.

Ventilation:

þ

¨

¨

There are gable end vents installed that allow adequate ventilation.

Insulation:

þ

¨

¨

Fiberglass battens.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 25 Report: 1943 SF - Sample Address: 433 Main Blvd

ELECTRICAL SYSTEM We are not electricians and in accordance with the standards of practice we only test a representative number of switches and outlets and do not perform load-calculations to determine if the supply meets the demand. However, every electrical deficiency or recommended upgrade should be regarded as a latent hazard that should be serviced as soon as possible, along with evaluation and certification of the entire system as safe by a licensed contractor. Therefore, it is essential that any recommendations that we may make for service or upgrades should be completed before the close of escrow, because an electrician could reveal additional deficiencies or recommend additional upgrades for which we disclaim any responsibility. Any electrical repairs or upgrades should be made by a licensed electrician. Aluminum wiring requires periodic inspection and maintenance by a licensed electrician. Smoke Alarms should be installed within 15 feet of all bedroom doors, and tested regularly. Operation of time clock motors is not verified. Inoperative light fixtures often lack bulbs or have dead bulbs installed. The inspector is not required to insert any tool, probe, or testing device inside the panels, test or operate any over-current device except for ground fault interrupters, nor dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels. Any ancillary wiring or system that is not part of the primary electrical distribution system is not part of this inspection but may be mentioned for informational purposes only, including but not limited to low voltage systems, security system devices, heat detectors, carbon monoxide detectors, telephone, security, cable TV, intercoms, and built in vacuum equipment.

Service: Type & Condition:

OK þ

MM RR ¨ ¨ Overhead, Appears serviceable.

Grounding Equipment:

þ

¨

¨

Not Visible.

Electrical Distribution Panels:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 26 Report: 1943 SF - Sample Address: 433 Main Blvd

Main Panel Location:

þ

Main Panel Observations:

Exposed view, Circuit and wire sizing correct so far as visible.

OK ¨

© Accredited Property Inspection

¨

¨

Exterior of house, north side, Appears serviceable 200 amp main breaker, 18 circuits, 40/240 to AC.

MM RR þ ¨ Missing handle tie/coupler at the 50/240 breaker for sub panel (MM) Correction recommended.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 27 Report: 1943 SF - Sample Address: 433 Main Blvd

OK þ

MM RR ¨ ¨ Located at the 2nd floor/south bedroom: Appears serviceable, 12 circuits Unable to remove panel cover for inspection, cover is painted/sealed to wall. Removal will cause damage to finish.

Entrance Cables:

þ

¨

¨

Aluminum- OK.

Branch Wiring:

þ

¨

¨

Copper, Appears serviceable.

General:

þ

¨

¨

A representative sampling of switches was tested. As a whole, switches throughout the house are in serviceable condition. Stored items prevent access and testing at some switches.

Garage Walls:

OK, Stored items prevent access and testing at some outlets and switches.

Subpanel #1:

Conductors:

Switches & Fixtures:

Electrical Outlets: General:

© Accredited Property Inspection

þ

¨

¨

A representative sampling of outlets was tested. As a whole, outlets throughout the house are in serviceable condition. Stored items prevent access and testing at some outlets.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 28 Report: 1943 SF - Sample Address: 433 Main Blvd

© Accredited Property Inspection

¨

¨

þ

OK ¨

MM RR þ ¨ No power, unable to reset GFCI (prior to finding the master outlet at the kitchen) This GFCI outlet was found to be redundant to kitchen GFCI ,LH side of sink.

¨

þ

¨

Non grounded outlet noted at exterior wall (patio door area), upgrades needed for safety. GFCI - inoperable, probably due to improper ground wire. Recommend further evaluation and correction by licensed electrician.

Recommend a full cover on exterior outlets with a dedicated plug.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 29 Report: 1943 SF - Sample Address: 433 Main Blvd

OK ¨

MM RR þ ¨ Ground Fault Circuit Interrupter (GFCI) outlets are recommended for installation at exterior areas. Outlet viewed at driveway area.

¨

þ

¨

GFCI - inoperable at north side exterior wall. Recommend further evaluation and correction by licensed electrician.

Kitchen Interior:

A representative sampling of switches and outlets was tested. As a whole, outlets and switches throughout the room are in serviceable condition.

Master Bath:

A representative sampling of switches and outlets was tested. As a whole, outlets and switches throughout the room are in serviceable condition.

Hall Bath:

A representative sampling of switches and outlets was tested. As a whole, outlets and switches throughout the room are in serviceable condition.

Guest Bath / 1st Floor:

A representative sampling of switches and outlets was tested. As a whole, outlets and

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 30 Report: 1943 SF - Sample Address: 433 Main Blvd

switches throughout the room are in serviceable condition. Laundry:

Electrical outlet is grounded, No 240 outlet.

Garage Walls:

A representative sampling of switches and outlets was tested. As a whole, outlets and switches throughout the house are in serviceable condition. Stored items prevent access and testing at some outlets and switches.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 31 Report: 1943 SF - Sample Address: 433 Main Blvd

HEATING - AIR CONDITIONING The inspector can only readily open access panels provided by the manufacturer or installer for routine homeowner maintenance, and will not operate components when weather conditions or other circumstances apply that may cause equipment damage. The inspector does not light pilot lights or ignite or extinguish solid fuel fires, nor are safety devices tested by the inspector. The inspector is not equipped to inspect furnace heat exchangers for evidence of cracks or holes, or inspect concealed portions of evaporator and condensing coils, heat exchanger or firebox, electronic air filters, humidifiers and de-humidifiers, ducts and in-line duct motors or dampers, as this can only be done by dismantling the unit. This is beyond the scope of this inspection. Thermostats are not checked for calibration or timed functions. Adequacy, efficiency or the even distribution of air throughout a building cannot be addressed by a visual inspection. Have these systems evaluated by a qualified individual. The inspector does not perform pressure tests on coolant systems, therefore no representation is made regarding coolant charge or line integrity. We perform a conscientious evaluation of the system, but we are not specialists. Please note that even modern heating systems can produce carbon monoxide, which in a poorly ventilated room can result in sickness and even death. Therefore, it is essential that any recommendations we make for service or further evaluation be scheduled before the close of escrow, because a specialist could reveal additional defects or recommend further upgrades that could affect your evaluation of the property, and our service does not include any form or warranty or guarantee. Normal service and maintenance is recommended on a yearly basis. Determining the presence of asbestos materials commonly used in heating systems can ONLY be preformed by laboratory testing and is beyond the scope of this inspection. Determining the condition of oil tanks, whether exposed or buried, is beyond the scope of this inspection. Leaking oil tanks represent an environmental hazard which is sometimes costly to remedy.

Heating Equipment: Type & Location:

Forced Air, Attic mounted.

Fuel Source:

Natural Gas.

Capacity / Approx. Age:

American Standard M# AUD100C960KO

General Operation & Cabinet:

OK þ

MM RR ¨ ¨ Appears serviceable.

Burners / Heat Exchangers:

þ

¨

¨

Burner Flame(s) appear typical.

Pump / Blower Fan:

þ

¨

¨

Appears serviceable.

Combustion Air:

þ

¨

¨

Combustion air is adequate.

© Accredited Property Inspection

100K BTU

2003?

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 32 Report: 1943 SF - Sample Address: 433 Main Blvd

Flues, Vents, Plenum:

þ

¨

¨

Air Filters:

OK ¨

MM RR þ ¨ The filter is in need of cleaning or replacement. Replacing or cleaning filters every 90 days is recommended.

The flue pipe is metal.

Viewed at hallway ceiling / 2nd floor. Normal Controls:

© Accredited Property Inspection

þ

¨

¨

Thermostat is located Hallway - 2nd floor.

in

the,

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 33 Report: 1943 SF - Sample Address: 433 Main Blvd

Fireplaces / Solid Fuel Heating: Living Room:

OK þ

MM RR ¨ ¨ Prefabricated metal with porcelain panels, Damper is operational, Gas system noted and serviceable. There are no glass doors installed. These could help minimize heat loss from the room when fireplace is not in use. When the fireplace is in use, they will eliminate embers from flying into the room and reduce the volume of room air sucked up the chimney.

¨

þ

¨

There is a visible build-up of creosote in the firebox or flue which indicates a need for cleaning. A professional chimney sweep should be consulted. Creosote is a tar-like substance that is created by burning wood fuels. It often lines the upper part of the firebox and flue. If not removed, this build-up can create a fire hazard. The age and condition of this fireplace is such that it should be fully inspected and evaluated by a licensed professional chimney sweep prior to use.

Air Conditioning: Primary Type:

Central.

Fuel Source:

240 Volt, Electrical disconnect present.

Capacity / Approx. Age:

Cold Point M# CNC60D80000A 07073057.

Supply Air Temp:

51 degrees.

© Accredited Property Inspection

5 ton

65 amp max breaker

2003? S#

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 34 Report: 1943 SF - Sample Address: 433 Main Blvd

System Condition:

Condensate Line:

þ

¨

¨

OK ¨

MM RR þ ¨ A whistling noise was present at the master bathroom register while AC was operating. The same noise was NOT present while operating the heater. Unable to determine the cause of this sound. You may choose to have further evaluation by a licensed HVAC specialist.

¨

þ

¨

Condensate lines installed.

þ

¨

¨

Flexible Round, Flow appeared serviceable. CFM not tested.

Appears serviceable, Recommend regular servicing.

Ductwork / Distribution: Ducts / Air Supply:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 35 Report: 1943 SF - Sample Address: 433 Main Blvd

PLUMBING SYSTEM Water quality or hazardous materials (lead) testing is available from local testing labs, and not included in this inspection. All underground piping related to water supply, waste, or sprinkler use are excluded from this inspection. Leakage or corrosion in underground piping cannot be detected by a visual inspection, nor can the presence of mineral build-up that may gradually restrict their inner diameter and reduce water volume. Plumbing components such as gas pipes, potable water pipes, drain and vent pipes, and shut-off valves are not generally tested if not in daily use. The inspector cannot state the effectiveness or operation of any anti-siphon devices, automatic safety controls, water conditioning equipment, fire and lawn sprinkler systems, on-site water quality and quantity, on-site waste disposal systems, foundation irrigation systems, spa and swimming pool equipment, solar water heating equipment, or observe the system for proper sizing, design, or use of materials. The water pressure within pipes is commonly confused with water volume, but whereas high water volume is good high water pressure is not. Therefore a regulator is recommended whenever street pressure exceeds 80 psi. However, regardless of pressure, leaks will occur in any system, and particularly in one with older galvanized pipes, or one in which the regulator fails and high pressure begins to stress washers and diaphragms within various components. Waste and drainpipes pipe condition is usually directly related to their age. Older ones are subject to damage through decay and root movement, whereas the more modern ABS ones are virtually impervious to damage, although some rare batches have been alleged to be defective. Older homes with galvanized or cast iron supply or waste lines can be obstructed and barely working during an inspection but later fail under heavy use. If the water is turned off or not used for periods of time (such as a vacant house waiting for closing), rust or deposits within the piping can further clog the piping system. However, inasmuch as significant portions of drainpipes are concealed, we can only infer their condition by observing the draw at drains at the time of inspection. Nonetheless, blockages will still occur in the life of any system.

Main Line: Shut Off:

Main shut-off valve is located, in front. Valve appears operational.

Material:

Copper.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 36 Report: 1943 SF - Sample Address: 433 Main Blvd

Pressure:

65 psi. Water pressure was checked at an exterior hose bib. Water pressure from 40 to 80 pounds per square inch is considered within normal/acceptable range.

Supply Lines: Material:

Copper.

Condition:

OK þ

MM RR ¨ ¨ Appears serviceable, Unable to view all connections.

Waste Lines:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 37 Report: 1943 SF - Sample Address: 433 Main Blvd

Material:

Plastic.

Condition:

OK þ

MM RR ¨ ¨ Lines not fully visible, Plumbing vents appear serviceable.

þ

¨

Hose Bibs / Hookups: General:

¨

Sample operated, appeared serviceable.

The temperature pressure relief valve at the upper portion of the water heater is a required safety valve which should be connected to a drain line of proper size terminating just above floor elevation. If no drain is located in the floor a catch pan should be installed with a drain extending to a safe location. The steam caused by a blow-off can cause scalding. Improper installations should be corrected.

Water Heater: Power Source:

Gas, Rheem 05/2014.

Capacity:

48 gallons.

Location:

Garage.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 38 Report: 1943 SF - Sample Address: 433 Main Blvd

Condition:

© Accredited Property Inspection

þ

¨

¨

OK ¨

MM RR ¨ ¨ A circulation pump was noted, not tested. Recommend regular inspection and maintenance.

¨

¨

¨

Appears serviceable, Pressure relief valve noted, not tested, Flue vent intact, A water shutoff valve is installed, Water heater is seismically secured.

A catch pan is recommended when installing water heaters over finished areas, or areas subject to moisture damage. Recommend installing a catch pan when replacing this unit.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 39 Report: 1943 SF - Sample Address: 433 Main Blvd

OK ¨

MM RR þ ¨ Vent flue is loose, or disconnected. Missing fasteners at the upper and lower joints. Recommend repairs by a qualified professional.

þ

¨

Fuel System: Meter / Tank:

© Accredited Property Inspection

¨

Meter located at exterior, north side, System appears serviceable Shut-off valve located at meter.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 40 Report: 1943 SF - Sample Address: 433 Main Blvd

¨

¨

¨

Earthquake safety shut-off device noted, not tested.

See Bathrooms section of report for information about plumbing and fixtures in those areas.

Fixtures & Drain Kitchen Sink:

OK þ

MM RR ¨ ¨ Porcelain, Faucet is serviceable.

¨

¨

¨

Under sink view, Viewing below the sink is restricted by stored items.

¨

¨

Plumbing appears serviceable, Not tested. There is a connection box installed in the wall with both hot and cold water and a drain pipe. The drain pipe was not flood tested.

Hose Bibs / Hookups/Sink Faucets: Laundry:

© Accredited Property Inspection

¨

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 41 Report: 1943 SF - Sample Address: 433 Main Blvd

KITCHEN - APPLIANCES We may test kitchen appliances for basic functionality, but cannot evaluate them for their performance nor for the variety of their settings or cycles. Appliances older than ten years may exhibit decreased efficiency. Even if general comments are made, these items are not inspected: free-standing appliances, refrigerators, freezers, ice makers, trash-compactors, built-in toasters, coffee-makers, can-openers, blenders, instant hot-water dispensers, water-purifiers, barbecues, grills, or rotisseries, timers, clocks, thermostats, the self-cleaning and cooking capability of ovens, and concealed or countertop lighting, which is convenient but often installed after the initial construction and not wired to national electrical standards. These items should be considered outside the scope of the inspection. Appliances are not moved during the inspection. Portable dishwashers are not inspected, as they require connection to facilitate testing.

Range/ Cooktop / Oven: Type & Condition:

OK þ

MM RR ¨ ¨ Range, Gas, Electric Appears serviceable.

þ

¨

ignition,

Ventilation: Type & Condition:

¨

External, Fan/Hood operational.

Refrigerator:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 42 Report: 1943 SF - Sample Address: 433 Main Blvd

Type & Condition:

þ

¨

¨

OK þ

MM RR ¨ ¨ Appears serviceable. Air gap device or high-loop is present on drain line- Proper.

þ

¨

Appears serviceable. Serviceability was based on the simple fact that the areas were getting cold. No technical evaluation was performed. Recommend regular maintenance for maximum performance and lifespan. Unable to verify the presence of an ice-maker, or view the line/valve area. Monitor area for signs of possible leakage (MM)

Dishwasher: Condition:

Garbage Disposal: Condition:

¨

Unit is serviceable, Wiring appears serviceable.

Kitchen Interior:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 43 Report: 1943 SF - Sample Address: 433 Main Blvd

Counters & Cabinets:

© Accredited Property Inspection

þ

¨

¨

Stone, Cabinets serviceable, with wear/damage.

appear minor

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 44 Report: 1943 SF - Sample Address: 433 Main Blvd

BATHROOMS In accordance with industry standards of practice, we do not comment on common cosmetic deficiencies, and do not evaluate window treatments, steam showers, and saunas. More importantly, we do we leak-test shower pans, which is usually the responsibility of a termite inspector. However, because of the possibility of water damage, most termite inspectors will not leak-test second floor shower pans without the written consent of the owners or occupants. Our inspection of interior areas includes the visually accessible areas of walls, floors, cabinets and closets, and a representative number of windows and doors, switches and outlets. We do not evaluate window treatments, nor move furniture, lift carpets or rugs, empty closets or cabinets, and we do not comment on common cosmetic deficiencies.

Sink & Cabinetry: Master Bath:

© Accredited Property Inspection

OK þ

MM RR ¨ ¨ Counters/cabinets serviceable.

¨

¨

¨

appear

Under sink view, Viewing below sink area is restricted. Primary condensate line noted. Right side.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 45 Report: 1943 SF - Sample Address: 433 Main Blvd

Hall Bath:

© Accredited Property Inspection

þ

¨

¨

OK ¨

MM RR ¨ ¨ Under sink view. Viewing below sink area is restricted.

¨

þ

¨

Counters/cabinets serviceable.

appear

Fittings are worn and corrosion is noted. Monitor and maintain.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 46 Report: 1943 SF - Sample Address: 433 Main Blvd

Guest Bath / 1st Floor:

© Accredited Property Inspection

OK þ

MM RR ¨ ¨ Counters/cabinets serviceable.

¨

¨

¨

Under sink view, Viewing below sink area is restricted.

¨

þ

¨

Leaks at faucet handles. A licensed plumber should be called to make further evaluation and repairs as needed.

appear

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 47 Report: 1943 SF - Sample Address: 433 Main Blvd

Toilet: Master Bath:

OK þ

Hall Bath:

þ

MM RR ¨ ¨ Appears serviceable, Toilet is water efficient type. ¨ ¨ Appears serviceable, Toilet is water efficient type.

Guest Bath / 1st Floor:

þ

¨

¨

Appears serviceable, Toilet is water efficient type.

þ

¨

¨

Appears serviceable Maintain sealant at all hardware to enclosure to avoid hidden water damage (MM)

¨

þ

¨

Minor leakage is noted at faucet handles (tub) Monitor and maintain.

Tub/Shower Fixtures: Master Bath:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 48 Report: 1943 SF - Sample Address: 433 Main Blvd

Hall Bath:

þ

¨

¨

OK þ

MM RR þ ¨ Whirlpool tub noted, not tested. API does not test whirlpool tubs. It is recommended that the lines be cleaned regularly to avoid bacterial contamination. Unit responded to power switch Unable to verify the presence/location of a GFCI protected power source. Recommend further evaluation by a qualified electrician to verify for safety. Cover panel not removed.

Appears serviceable.

Tub/Shower And Walls: Master Bath:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 49 Report: 1943 SF - Sample Address: 433 Main Blvd

© Accredited Property Inspection

¨

þ

¨

OK ¨

MM RR þ ¨ Cosmetic moisture damage is noted at the wall or floor outside the tub/shower area. Area viewed near leaking tub handles.

þ

¨

¨

Caulk and seal all tub, shower, and floor areas as a precaution. Grout needs some maintenance at the tub area.

Shower walls appear serviceable, Enclosure appears serviceable.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 50 Report: 1943 SF - Sample Address: 433 Main Blvd

Hall Bath:

© Accredited Property Inspection

OK ¨

MM RR þ ¨ Mildew noted in area, recommend cleaning and disinfecting on a regular basis (MM)

þ

¨

¨

Enclosure appears serviceable.

¨

þ

¨

Cosmetic moisture damage is noted at the wall or floor outside the tub/shower area. Caulk and seal all tub, shower, and floor areas as a precaution.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 51 Report: 1943 SF - Sample Address: 433 Main Blvd

Bath Ventilation: Master Bath:

OK þ

MM RR ¨ ¨

Hall Bath:

þ

¨

¨

Only a window is provided for ventilation.

Guest Bath / 1st Floor:

þ

¨

¨

Only a window is provided for ventilation.

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 52 Report: 1943 SF - Sample Address: 433 Main Blvd

INTERIOR ROOMS Our inspection of living space includes the visually accessible areas of walls, floors, cabinets and closets, and the testing of a representative number of windows and doors, switches and outlets. We do not evaluate window treatments, move furnishings or possessions, lift carpets or rugs, empty closets or cabinets, nor comment on cosmetic deficiencies. We may not comment on cracks that appear around windows and doors, along lines of framing members or along seams of drywall and plasterboard. These are typically caused by minor movement, such as wood shrinkage, common settling, and seismic activity, and will often reappear if they are not correctly repaired. Such cracks can become the subject of disputes, and are therefore best evaluated by a specialist. Floor covering damage or stains may be hidden by furniture, and the condition of floors underlying floor coverings is not inspected. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lighting conditions. Check with owners for further information. All fireplaces should be cleaned and inspected on a regular basis to make sure that no cracks have developed. Large fires in the firebox can overheat the firebox and flue liners, sometimes resulting in internal damage. Testing, identifying, or identifying the source of environmental pollutants or odors (including but not limited to lead, mold, allergens, odors from household pets and cigarette smoke) is beyond the scope of our service, but can become equally contentious or difficult to eradicate. We recommend you carefully determine and schedule whatever remedial services may be deemed advisable or necessary before the close of escrow.

Doors: Main Entry Door:

OK þ

MM RR ¨ ¨ Serviceable, Hardware operational.

Other Exterior Doors:

þ

¨

© Accredited Property Inspection

¨

Standard side/rear Appears serviceable.

doors.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 53 Report: 1943 SF - Sample Address: 433 Main Blvd

© Accredited Property Inspection

¨

¨

¨

OK þ

MM RR ¨ ¨ French doors viewed at 2nd floor balcony, Appears serviceable.

Doors viewed at sides are permanently closed. (north side viewed)

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 54 Report: 1943 SF - Sample Address: 433 Main Blvd

© Accredited Property Inspection

¨

þ

¨

OK ¨

MM RR þ ¨ Door hardware needs some adjustment or repair for it to function appropriately (loose knob, etc.)

French doors viewed at 2nd floor balcony: Moisture damage noted a base areas. Make repairs and maintenance as needed.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 55 Report: 1943 SF - Sample Address: 433 Main Blvd

Overall Interior Door Condition:

þ

¨

¨

OK þ

MM RR ¨ ¨ Wood, Insulated glass, Casement, A representative sampling was taken. Windows as a grouping are generally operational.

A representative sampling was taken. Doors appear to be generally serviceable.

Windows: General Type & Condition:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 56 Report: 1943 SF - Sample Address: 433 Main Blvd

þ

Hall Bath:

OK.

Guest Bath / 1st Floor:

OK.

General Material & Condition:

OK þ

¨

¨

A representative sampling was taken. Windows as a grouping are generally operational.

Walls: MM RR ¨ ¨ Drywall, General condition appears serviceable, Stored items or furnishings prevent full inspection.

Ceilings:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 57 Report: 1943 SF - Sample Address: 433 Main Blvd

General Type & Condition:

þ

¨

¨

OK þ

MM RR ¨ ¨ Rugs and floor coverings prevent viewing of primary floor materials, Stored items or furnishings prevent full inspection.

Drywall, General condition appears serviceable.

Floors: General:

Stairs & Handrails:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 58 Report: 1943 SF - Sample Address: 433 Main Blvd

Condition:

þ

¨

¨

OK þ

MM RR ¨ ¨ Smoke alarm(s) responded to test button operation.

Interior stairs serviceable, Stair handrail serviceable.

Smoke / Fire Detector: General:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 59 Report: 1943 SF - Sample Address: 433 Main Blvd

LAUNDRY AREA Laundry appliances are not tested or moved during the inspection and the condition of any walls or flooring hidden by them cannot be judged. Drain lines and water supply valves serving washing machines are not operated. Water supply valves may be subject to leaking if turned. See Plumbing and Electrical pages for more details about those types of system components.

Laundry: Location:

Service area main floor.

Fuel System:

OK ¨

© Accredited Property Inspection

MM RR ¨ ¨ Gas service pipe is provided.

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 60 Report: 1943 SF - Sample Address: 433 Main Blvd

Clothes Washer:

OK ¨

MM RR ¨ ¨ Washer was not operated at the time of inspection.

Clothes Dryer:

¨

¨

Dryer Vent:

A dryer vent is provided, Recommend regular service to keep lint clear in line.

¨

Dryer was not operated at the time of inspection.

Vent viewed at south side. Unable to view duct under the structure (crawlspace)

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 61 Report: 1943 SF - Sample Address: 433 Main Blvd

GARAGE - CARPORT Determining the heat resistance rating of firewalls is beyond the scope of this inspection. Flammable materials should not be stored within closed garage areas. Garage door openings are not standard, so you may wish to measure the opening to ensure that there is sufficient clearance to accommodate your vehicles. It is not uncommon for moisture to penetrate garages, particularly with slabs on-grade construction, and this may be apparent in the form of efflorescence or salt crystal formations on the concrete. You may want to have any living space above the garage evaluated further by a structural engineer, as it may be seismically vulnerable.

Type: Attached, One car Occupant belongings noted, unable to fully view area.

Roof: Condition:

OK ¨

MM RR ¨ ¨ See notes in the Balcony section.

þ

¨

¨

There appears to be a fire rated separation between the garage ceiling and the living areas above.

þ

¨

¨

Wood. Roll Up.

Ceilings: Condition:

Garage Door: Material - Condition:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 62 Report: 1943 SF - Sample Address: 433 Main Blvd

Door Operator:

þ

¨

¨

Service Doors:

OK þ

MM RR ¨ ¨ Serviceable, Hardware operational, There is a fire rated door separating the garage from the living areas of the house. Self closing device noted and operational.

Automatic door opener(s)operational, Automatic reverse feature is, operational.

Garage Walls:

© Accredited Property Inspection

Confidential - for client use only. Use by any unauthorized persons is prohibited.

Page 63 Report: 1943 SF - Sample Address: 433 Main Blvd

Type & Condition:

þ

þ

¨

OK ¨

MM RR ¨ ¨ Same as above.

Drywall, General condition appears serviceable Unable to fully inspect, due to occupant belongings, and/or wall covering.

Fire Wall

The wall covering appears to meet the minimum fire separation standards.

Condition:

þ

Floor:

© Accredited Property Inspection

¨

¨

Appears serviceable, Floor is not fully visible, due to stored items.

Confidential - for client use only. Use by any unauthorized persons is prohibited.